Interim Report, Construction Deficiencies in FHA Single Family Homes, Merced, CA

Published by the Department of Housing and Urban Development, Office of Inspector General on 1996-09-24.

Below is a raw (and likely hideous) rendition of the original report. (PDF)

                       U.S. Department of Housing and Urban Development
                                                Pacific/Hawaii
                                    Office of Inspector General for Audit
                                  450 Golden Gate Avenue, P.O. Box 36003
                                   San Francisco, California 94102-3448



                                        September 24, 1996

                                                                 AUDIT RELATED MEMORANDUM
                                                                 96-SF-229-1809

MEMORANDUM FOR:                Yvielle Edwards-Lee, Fresno Area Coordinator, 9BS



FROM:                          Gary E. Albright, District Inspector General for Audit, 9AGA


SUBJECT:                       Interim Report
                               Construction Deficiencies in FHA Single Family Homes
                               Merced, California


                                          INTRODUCTION

        We are issuing this interim report to alert you to significant concerns about construction
deficiencies in FHA insured single family homes in the City of Merced, California.

        Over the last few months, our office has reviewed many homeowner concerns involving the
accelerated deterioration of insured (and uninsured) homes built in certain Merced subdivisions.
Homeowners reported their homes had experienced settlement problems resulting in cracked
foundations, walls separated from foundations and other construction deficiencies. These conditions
create unsafe living conditions, increase the FHA's financial exposure for insured homes, and may
indicate a pattern of substandard construction. More importantly, homeowner health problems may
be directly related to the construction deficiencies.

        Our review confirmed that homes in at least two Merced subdivisions are suffering from serious
settlement problems. As a result of these conditions, the local assessor's office has already reduced
the value of two homes to zero. Certain homes with construction deficiencies also contain mold and
spores which have affected or may affect the health of the FHA homeowners.

         The two subdivisions were inspected, processed and approved using the Veterans Affairs
Master Certificate of Reasonable Value (VA-MCRV) process. The contractors, VA fee inspectors, and
City of Merced inspectors certified all the homes complied with Minimum Property Standards and the
Uniform Building Codes (UBC). During our review, we obtained engineering reports which refute
these certifications and state that either the soils were not properly prepared prior to construction
and/or foundations were not built to code. As a result, some FHA homes are deteriorating at an
accelerated rate. This deterioration increases the risk of default and subsequent loss to the FHA
insurance fund, and poses a threat to the health and safety of homebuyers. The conditions disclosed
thus far indicate the need to address current risks and limit future exposure for both FHA and the
homeowners.


                                          BACKGROUND
        Subdivisions processed using VA-MCRV procedures are inspected by Veteran Affairs fee
inspectors and the City of Merced Planning Department personnel. These VA and local inspections,
provided at sequential stages of construction, are to provide assurances to VA and HUD that newly
constructed homes meet local building codes and Minimum Property Standards as required by 24 CFR
200.926. In addition, the contractor certifies to FHA compliance with HUD Minimum Property
Standards and HUD Handbook 4145.1 REV-2, Architectural Processing & Inspections for Home
Mortgage Insurance including Appendix 8, Site Grading & Drainage Guidelines, and local building
codes.

        The conditions cited in this report involve FHA, VA, and CalVet insured mortgages, as well as
conventional mortgages. Within FHA insurance, there are provisions in 24 CFR 200.500 for
assistance to eligible homeowners to correct structural defects within four years of issuance of the first
mortgage certificate. Older homes do not qualify for this assistance.

                                         REVIEW RESULTS

        Our review shows that the contractor did not always comply with either the Uniform Building
Codes or HUD Minimum Property Standards. We compared soils report recommendation
requirements with conclusions reached by geotechnical engineers hired to determine the cause of
settlement experienced by homes in the subdivisions. The reports concluded that settlement problems
were caused by contractors either ignoring certain soils report recommendations or not complying with
the UBC. Our review included the following two subdivisions:

1. Campus North 1 and 2. Of the approximately 109 homes in this subdivision, at least 55 are FHA
insured. Twenty of the homeowners (including 12 FHA homeowners) have filed suit against the
contractor because of faulty construction. Our inspection of two FHA insured homes showed cracking
exteriors, a sagging roof and a large accumulation of mold inside the homes. These conditions are
alarming considering the homes are three to four years old. A September 11, 1996 inspection report
completed by soils and foundation engineers concluded:

"...there is widespread evidence of excessive moisture coming from the slab. Based on these two
corings, it seems likely to us that there is an inadequate capillary break in drainage of the underslab
area. This has resulted in the moisture barrier being subjected to actual water intrusion, which it is not
designed to withstand". The report further stated the lack of adequate capillary break "... does answer
the question of how water is able to get through and damage the slab." The engineers indicated more
work should be required to evaluate the capillary break.

2. Village Landing. These 189 homes were built approximately 10 years ago in two phases. There
are currently at least 18 FHA insured homes in this subdivision. Fourteen homeowners (3 FHA) have
sued the contractor because of faulty construction. Homeowners have complained about serious wall
and slab cracking, and accumulations of mold. Walls are separating from the slab floor, the linoleum
is discolored, and the interiors are deteriorating. Residents have moved out of two homes because
of the health related conditions discussed below. Because of their deteriorated condition, the County
Assessor has appraised both homes at zero value. We obtained several engineering reports to
determine the extent of problems with the homes. Following are synopses of two engineering reports:

        An August 12, 1996 report from an environmental geology and engineering firm stated:

"The purpose of this investigation was to determine the general conformance of the construction of the
residence to the specifications set forth in the soils report...dated November 21, 1984....The


                                                    2
footing...was found to be embedded 11-3/4 inches, or 6-1/4 inches less than what was recommended.
Footings that were excavated by [another company] report embedments of 10 inches on the east, 12
inches on the west, 11 inches on the south and 10 inches on the north side of the residence."

         The report further stated the contractor apparently used 10 gauge wire mesh in the slab versus
the 6 gauge specified. The purpose of the wire mesh in concrete slabs is to minimize the potential for
large slab cracks to develop and propagate completely all of the way through the slab, thereby
preventing the intrusion of vermin and water. The report also states "The reason that this slab cracked
all the way through to the sub-base is that the steel was placed at the bottom of the slab and provided
no structural resistance to prevent the crack from forming. Structural steel placed at the bottom of a
slab is a construction defect."

         Another engineering report dated October 12, 1995 for another home in the subdivision stated
the following:

"...all of the damage in your house was due to up and down movement as a result of seasonal
moisture changes in the underlying expansive clay soil...the foundation of your house was improperly
constructed. It does not meet the minimum depth levels required by the (UBC)... had the footings
been built to the proper depth, the amount of movement suffered would have been much less." The
contractor failed to use crushed rock under the foundation of the house, "... and the foundation only
extended about 6 inches into grade, but the (UBC) required that footings penetrate at least twelve
inches into grade."

       We are awaiting the results of 13 engineering reports on other homes in this subdivision.

Health Concerns: In addition to the structural issues, there are potential health concerns. The
presence of excessive moisture within some homes has allowed the growth of mold/fungi. Long
thought to be solely a cosmetic problem, it is now known that mold/fungi exposure may cause allergies
and asthma including potentially life threatening allergic responses such as hypersensitivity
pneumonitis. A new and alarming concern is that toxicoses may be resulting from exposure to molds
capable of producing toxic substances which suppress immunity and can affect other vital organ
systems including the nervous system. Reports suggesting this possibility are arising all over the
country, are being studied by the Center for Disease Control and are the subject of considerable
discussion both nationally and internationally at professional conferences. As noted, adverse health
conditions tend to be principally of a respiratory and/or allergenic nature and are especially serious
for children. Other effects can range from minor to severe illness particularly after long exposure.
Numerous exposed individuals have reported inability to work due to loss of mental capacity and
extreme fatigue.

         The incidences of mold/fungi have been detected under carpets and linoleum at several homes
in the Merced subdivisions. The Director, Merced Division of Environmental Health has conducted
over 30 inspections of homes for mold/fungi and identified three houses with the highest
concentrations. Laboratory reports revealed levels of aspergillus, penicillium, stachybotrys and
cladosporium species from samples taken from the three homes. In May, 1996 the Director alerted the
builder of these homes in an attempt to speed repair work to correct the moisture intrusion. To date
the builder has not undertaken any repairs. Family members of one home whose physician advised
them to vacate a house ..."so obviously full of mold", have since been tested and found to have
evidence of stachybotrys exposure in their blood. The Merced Director of Environmental Health
reported this to the California Environmental Protection Agency, Department of Toxic Substances
Control, stating that he had told people with mold/fungi problems that "mold/fungi growth inside the


                                                  3
home can be a potential health hazard". Another physician has attributed a child's serious respiratory
problems to living in a damp house "secondarily colonized by ...fungi or mold", and stated, "the house
she lives in is a hazard to her health". A report by an environmental geology and engineering firm,
analyzing one home's moisture problems, reported "The development of molds and mildews in
residences is common in subdivisions where the slabs are not sealed properly. Often these molds and
mildews will aggravate existing health problems of family members, or will create new ones."

                                             SUMMARY

         The cited conditions have serious implications, considering the accelerated home deterioration
and the effect on the homeowners' health and safety. The certifications by builders and inspections
by both the City of Merced and Veterans Affairs fee inspectors are questionable based on a
comparison of building standards to subsequent engineering reports. While our immediate concern
is with the existing homeowners, corrective action must also be applied to future construction. The City
of Merced is currently processing a development called Bellevue Ranch which involves between 4,800
and 6,600 residential dwelling units.

       Before we issue a final report, we need to complete additional research into the extent and
sources of construction deficiencies, and gather additional data on the health risks for the
homeowners. We expect to issue a final report by December 1996.

       In the interim, we need to work closely with your staff, and consider an effective method to
make existing and potential homeowners aware of construction deficiencies, potential health risks, and
any available assistance to remedy construction deficiencies (such as the assistance available under
24 CFR 200.500 for homes less than four years old).

         Within 30 days, we are requesting that you provide my office with a response to the conditions
cited in this interim report - and any suggestions to improve existing home construction practices in
the City of Merced. If you have any questions, or would like to discuss our ongoing review, please call
me at (415) 436-8101.




                                                   4
                                       DISTRIBUTION

Secretary's Representative, Pacific/Hawaii, 9AS (2)
Fresno Area Coordinator, 9BS
Chief, Production REO Branch, Fresno, 9BHSC
Director, Office of Housing, 9AH
Office of Comptroller (Attn: K.J. Brockington),Texas State Office,6AF
Chief Counsel, Sacramento,CA, 9GC
Assistant General Counsel, California State Office, 9AC
Housing-FHA Comptroller, HF (2)
Assistant Secretary for Housing-Federal Housing Commissioner,H (Rm 9100) (2)
Deputy Assistant Secretary for Single Family Housing Programs, HS (Rm 9282) (2)
Director, Office of Single Family Housing, HSI (Room 9282) (2)
Deputy Chief Financial Officer for Finance, FF (Room 10166) (2)
Chief Financial Officer, F (Room 10164) (2)
Director, Participation and Compliance Division, HSLP (Room 6274)
Director, Division of Housing Finance Analysis, TEF (Room 8212)
Assistant to the Deputy Secretary for Field Management, SDF (Room 7106)
Special Assistant, Office of Public Affairs, WR (Room 10136)
Helen Stackhouse, Audit Liaison Officer, HF (Room 5130)(5)
William Eargle, Audit Liaison Officer, AF (Room 10164) (4)




                                              5